| Voltage Stabilisation | Independent phase control |
| Output voltage selectable via display , PC and/ or Ethernet * | from 210 to 255V (L-N) from 360 to 440V (L-L) |
| Output voltage accuracy | ± 0,5% |
| Frequency | 50Hz ±5% or 60 Hz ±5% |
| Admitted load variation | Up to 100% |
| Admitted load imbalance | 100% |
| Cooling | Natural air ventilatioin. From 35° C aided with fans |
| Ambient temperature | -25/+45 C |
| Storage temperature | -25/+60 C |
| Max relative humidity | 95% (non condensing) |
| Admitted overload | 200% 2 min. |
| Harmonic distortion | None introduced |
| Colour | RAL 7035 |
| Protection degree | IP 21 |
| User interface | 10″ touch panel (multilingual) remotely available via VNC |
| Installation | Indoor |
| Regulator overload protection | Digital control |
| Communication system | Ethernet / USB / MODBUS TCP/ Ip |
| Overvoltage protection | Class I input surge arrestor Class II output surge arrestor Optimal voltage return through supercapacitors in case of blackout |